Commissioning (via operating menu) Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
42 Endress+Hauser
7. Setup → Medium group
Select medium group (Others or Water based (DC >= 4))
8. Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
9. Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
10. Setup → Level
Displays the measured level L.
11. Setup → Distance
Displays the distance D between the reference point R and the level L.
12. Setup → Signal quality
Displays the signal quality of the level echo.
13. Setup → Mapping → Confirm distance
Compare the displayed distance to the real distance in order to start the recording
of the mapping curve
2)
.
2) For FMP54 with gas phase compensation (product structure: feature 540 "Application Package", option EF or EG)
a map must NOT be recorded.