Commissioning (via operating menu) Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
44 Endress+Hauser
4.
Setup  →  Operating mode
3)
Select the Interface option.
5. Setup  →  Tank type
Select tank type.
6. Setup  →  Tube diameter (only if "Tank type" = "Bypass / pipe")
Enter the diameter of the bypass or stilling well.
7. Setup  →  Tank level
Select tank level (Partially filled oder Fully flooded)
8. Setup  →  Distance to upper connection
In bypasses: Enter distance from reference point R to lower edge of the upper
connection; otherwise: Keep the factory setting
9. Setup  →  DC value
Enter dielectric constant of the upper medium.
10. Setup  →  Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
11. Setup  →  Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
12. Setup  →  Level
Displays the measured level L
L
.
13. Setup  →  Interface
Displays the interface height L
I
.
14. Setup  →  Distance
Displays the distance D
L
between the reference point R and the level L
L
.
15. Setup  →  Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
16. Setup  →  Signal quality
Displays the signal quality of the level echo.
17. Setup  →  Mapping  →  Confirm distance
Compare the displayed distance to the real distance in order to start the recording
of the mapping curve.