Levelflex FMP55
Endress+Hauser 13
Input
Measured variable
The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of
linearization (32 points).
Measuring range
The maximum measuring range is:
• for rope probe in bypass or stilling well up to 10 m (33 ft)
• for rod probe in bypass or stilling well up to 4 m (13 ft)
• for coax probe up to 6 m (20 ft)
• Reduction of the max. possible measuring range through buildup, above all of moist products.
• Due to the high diffusion rate of ammonia it is recommended with gas-tight bushing
3)
for
measurements in this medium.
3) optionally available for FMP55