Levelflex FMP55
38 Endress+Hauser
-80 (-3.15)
-60 (-2.36)
-40 (-1.57)
-20 (-0.79)
0
20 (0.79)
40 (1.57)
60 (2.36)
80 (3.15)
0
DC = 80
A
D
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
20 (0.79)
250 (9.84)
300 (11.8)
A0021482
20 Measuring error at the end-of-probe for rope probes
A Distance from probe end
D Measuring error: Sum of non-linearity, non-repeatability and hysteresis
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm from end of probe; lower blocking distance).
In the area of the upper probe end, the measuring error is as follows (rod/rope only):
2 (0.08)
0 (0)
- 2 (- 0.08)
100 (3.94) 200 (7.87)
10 (0.39)
- 10 (-0.39)
30 (1.18)
- 30 (- 1.18)
40 (1.57)
- 40 (- 1.57)
R
D
DC = 2
DC = 80
A0015091
21 Measuring error at the upper end of the probe; dimensions: mm (in)
D Sum of non-linearity, non-repeatability and hysteresis
R Reference point of measurement
DC Dielectric constant
Resolution
• digital: 1 mm
• analog: 1 μA