Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x1122
HART specification 7.0
Device description files (DTM,
DD)
Information and files at:
www.endress.com
www.fieldcommgroup.org
HART load Min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
Level linearized
Distance
Interface
Interface distance
Upper interface thickness
Electronic temperature
Measured capacity
Relative echo amplitude
Relative interface amplitude
Measured values for SV, TV, FV (second, third and fourth variable)
Level linearized
Distance
Interface linearized
Interface distance
Upper interface thickness
Terminal voltage
Electronic temperature
Measured capacity
Absolute echo amplitude
Relative echo amplitude
Absolute interface amplitude
Relative interface amplitude
Calculated DC
Supported functions Burst mode
Additional transmitter status
Wireless HART data
Minimum start-up voltage
for device version "2-wire; 4-20mA HART"
1)
: 17.5 V
Minimum start-up voltage for any other device version: 16.0 V
Start-up current 3.6 mA
Start-up time 45 s
Minimum operating
voltage
11.4 V
Multidrop current 3.6 mA
Set-up time 1 s
1) Ordering feature 020: "Power supply; output", option A