Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x1122
HART specification 7.0
Device description files (DTM,
DD)
Information and files at:
• www.endress.com
• www.fieldcommgroup.org
HART load Min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Interface
• Interface distance
• Upper interface thickness
• Electronic temperature
• Measured capacity
• Relative echo amplitude
• Relative interface amplitude
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Interface linearized
• Interface distance
• Upper interface thickness
• Terminal voltage
• Electronic temperature
• Measured capacity
• Absolute echo amplitude
• Relative echo amplitude
• Absolute interface amplitude
• Relative interface amplitude
• Calculated DC
Supported functions • Burst mode
• Additional transmitter status
Wireless HART data
Minimum start-up voltage
for device version "2-wire; 4-20mA HART"
1)
: 17.5 V
Minimum start-up voltage for any other device version: 16.0 V
Start-up current 3.6 mA
Start-up time 45 s
Minimum operating
voltage
11.4 V
Multidrop current 3.6 mA
Set-up time 1 s
1) Ordering feature 020: "Power supply; output", option A