Levelflex M FMP40 FOUNDATION Fieldbus Mounting
Endress+Hauser 15
Installation in horizontal and upright
cylindrical tanks
Use the following types of probe for
measuring ranges
up to 4 m (13 ft): rod probe (1) or coax
probe (2)
up to 10 m (33 ft): separable probe
above 10 m (33 ft): 4 mm rope probe
Installation and possible fixing as with
bulk solids.
Any distance from wall, as long as
occasional contact is prevented.
When installing in tanks with a lot of
internals or internals situated close to the
probe,or in connection with large :
Use a coax probe!
L00-FMP4xxxx-17-00-00-yy-021
1
2
Installation in stilling well or bypass
A rod probe can be used for pipe diameters
bigger than 40 mm.
When installing a rod probe into a metallic
pipe with internal diameter of up to
150 mm, you have all the advantages of a
coax probe.
Welded joints that protrude up to approx.
5 mm inwards do not influence
measurement.
If a rod probe is used, the probe length
must be 100 mm longer than the lower
disposal.
It must be ensured that the probe does not
come into contact with the side wall.
Where necessary, use a centering disk at
the lower end of the probe (see Operating
Instruction on the CD-ROM).
L00-FMP4xxxx-17-00-00-xx-024
min. 100