Commissioning Levelflex M FMP40 FOUNDATION Fieldbus
38 Endress+Hauser
dist. too small
• At the moment, an interference is being evaluated
• Therefore, a mapping is carried out including the presently measured echoes
• The range to be suppressed is suggested in the "range of mapping" (052) function
dist. too big
• This error cannot be remedied by interference echo mapping
• Check the application parameters (002), (003), (004) and "empty calibr." (005).
dist.unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in
the "range of mapping" (052) function.
"
Caution!
The range of mapping must end 0.3 m (20") before the echo of the actual level. In case of empty
vessel it is possible to make a map over the whole probe length.
probe free
If the probe is uncovered, mapping is carried out along the whole probe length.
"
Caution!
Only begin mapping in this function if the probe is safely uncovered. Otherwise, the device will
not make correct measurements!
5.4.15 Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always the
reference point of the measuremen (→ ä 28). This value can be edited by the operator.
For manual mapping, the default value is 0,3 m.
⇒