Levelflex M FMP40 FOUNDATION Fieldbus Commissioning
Endress+Hauser 39
5.4.16 Function "start mapping" (053)
This function is used to start the interference echo mapping up to the distance given in "range
of mapping" (052).
Selection:
off: no mapping is carried out
on: mapping is started
5.4.17 Function "dist./meas.value" (008)
The distance measured from the reference point to the product surface and the meas. value
calculated with the aid of the empty alignment are displayed again. Check whether the values
correspond to the actual meas. value or the actual distance. The following cases can occur:
Distance correct – meas. value correct È basic setup completed
Distance incorrect – meas. value incorrect È a further interference echo mapping must be
carried out "check distance" (051).
Distance correct – meas. value incorrectÈ check "empty calibr." (005)
!
Note!
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("envelope curve" (0E) function group) is recommended ( ä 42).