Micropilot FMR10
10 Endress+Hauser
Power supply failure
The configuration remains stored in the sensor.
Connecting the device
2
Y
+ +
- -
I
1
mA
A0028907
 4 FMR10 block diagram
1 Micropilot FMR10, 4 to 20 mA
2 Power supply
Cable specification
Unshielded cable, wire cross-section 0.75 mm
2
Resistant to UV and weather conditions as per ISO 4892-2
Flame resistance according to IEC 60332-1-2
As per IEC/EN 60079-11 section 10.9, the cable is designed for a tensile strength of 30 N (6.74 lbf)
(over a period of 1 h).
The device is supplied with 10 m (33 ft) cable length as standard.
Overvoltage protection
The device is equipped with integrated overvoltage protection.
Performance characteristics
Reference operating
conditions
Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
Humidity = 60 % ±15 %
Reflector: metal plate with diameter ≥ 1 m (40 in)
No major interference reflections inside the signal beam
Maximum measured error
Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to
the span.
Output, digital
(HART, SmartBlue (app))
Sum of non-linearity, non-repeatability and hysteresis: ±5 mm (±0.2 in)
Offset/zero point: ±4 mm (±0.16 in)
Output, analog
Only relevant for 4-20mA current output; add error of the analog value to the digital value
Sum of non-linearity, non-repeatability and hysteresis: ±0.02 %
Offset/zero point: ±0.03 %