EasyManua.ls Logo

Endress+Hauser Micropilot FMR10 - 5 Installation; 5.1 Installation conditions

Endress+Hauser Micropilot FMR10
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR10
Endress+Hauser 13
Mounting outside the nozzle
D: min. 40 mm (1.5 in)
L: max. D × 1.5
Mounting inside the nozzle
D: min. 80 mm (3 in)
L: max. 140 mm (5.5 in) + D × 1.5
Position for installation on a vessel
A
BD
D
A0028410
 8 Installation position on a vessel
If possible install the sensor so that its lower edge projects into the vessel.
Recommended distance A wall - nozzle outer edge: ~ ¹⁄₆ of the vessel diameter D. Under no
circumstances should the device be mounted closer than 15 cm (5.91 in) to the vessel wall.
Do not install the sensor in the middle of the vessel.
Avoid measurements through the filling curtain.
Avoid equipment such as limit switches, temperature sensors, baffles, heating coils etc.
No signals are evaluated within the Blocking distance (BD). It can therefore be used to suppress
interference signals (e.g. the effects of condensate) in the vicinity of the antenna.
An automatic Blocking distance of at least 0.1 m (0.33 ft) is configured as standard. However, this
can be overwritten manually (0 m (0 ft) is also permitted).
Automatic calculation:
Blocking distance = Empty calibration - Full calibration - 0.2 m (0.656 ft).
Each time a new entry is made in the Empty calibration parameter or Full calibration parameter,
the Blocking distance parameter is recalculated automatically using this formula.
If the result of the calculation is a value < 0.1 m (0.33 ft), the Blocking distance of 0.1 m (0.33 ft)
will continue to be used.
Device alignment for installation on a vessel
Align the antenna vertically to the product surface.
Align the eyelet with lug towards the vessel wall as well as possible.

Table of Contents

Other manuals for Endress+Hauser Micropilot FMR10

Related product manuals