Micropilot FMR10
16 Endress+Hauser
Use of flooding protection tube
The flooding protection tube ensures the sensor measures the maximum level even if it is completely
flooded.
In free-field installations and/or in applications where there is a risk of flooding, the flooding
protection tube must be used.
The flooding protection tube can be ordered as an accessory or together with the device via the
product structure "Accessory enclosed".
1
2
3
4
A0030394
 13 Function of flooding protection tube
1 Air pocket
2 O-ring (EPDM) seal
3 Blocking distance
4 Max. level
The tube is screwed directly onto the sensor and seals off the system by means of an O-ring making
it air-tight. In the event of flooding, the air pocket that forms in the tube ensures the measurement
of the maximum level at the end of the tube. Due to the fact that the Blocking distance is inside the
tube, multiple echoes are not analyzed.
Installation with mounting bracket, adjustable
The mounting bracket is available as an accessory.
A0040057
 14 Installation with mounting bracket, adjustable
Wall or ceiling installation is possible.
Using the mounting bracket, position the antenna so that it is perpendicular to the product
surface.