XA01555F-A Micropilot FMR60, FMR62, FMR67
20 Endress+Hauser
Modifications to the device can affect the explosion protection and must be carried out by staff
authorized to perform such work by Endress+Hauser.
Refer to the temperature tables for the relationship between the permitted ambient temperature
for the sensor and/or transmitter, depending on the range of application and the temperature
class.
When using in hybrid mixtures (gas and dust occurring simultaneously), observe additional
measures for explosion protection.
Safety instructions:
Special conditions
Permitted ambient temperature range at the electronics housing:
–40 °C ≤ T
a
≤ +80 °C
Observe the information in the temperature tables.
In the case of process connections made of polymeric material or with polymeric coatings, avoid
electrostatic charging of the plastic surfaces.
In the event of additional or alternative special varnishing on the housing or other metal parts:
Observe the danger of electrostatic charging and discharge.
Do not rub surfaces with a dry cloth.
Avoid electrostatic charging of the sensor (e.g. do not rub dry and install outside the filling flow).
Device type FMR67 and Basic specification, Position 11-13 (Process Connection) = XxA
Changing the position of the alignment device must be impossible:
After the alignment of the antenna via the pivot bracket
After tightening of the clamping flange
After setting the damping ring (torque 15 Nm)
Degree of protection IP67 must be fulfilled.
Device type FMR67 and Basic specification, Position 14 (Air Purge Connection) = 1, 2
If equipment with Ga/Gb or Da/Db is required: In the closed state the minimum degree of
protection of the installation must be IP67.
After removing the air purge connection: Lock the opening with a suitable plug.
Torque: 6-7 Nm
For Da/Db: thread engagement > 5 turns
Degree of protection IP67 must be fulfilled.
Safety instructions:
Installation
A
2
1
1
4
5
3
A0031938
 2
A Zone 1, Zone 21
1 Potential equalization line
2 Electronic insert
3 Certified associated apparatus
4 Tank; Zone 0, Zone 1 or Zone 20, Zone 21
5 Potential equalization