EasyManua.ls Logo

Endress+Hauser nivotester FTC 420 - Technical Data; Operating Temperature; Relay

Endress+Hauser nivotester FTC 420
36 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
MechanicalHousing: Minipac housing, light grey plastic with blue front panel
Protection IP 40
Dimensions: 113 mm x 50 mm x 75 mm
Weight: approx. 0.3 kg
Mounting rail: EN 50 022-35x15 or EN 50 022-35x7.5 (Top hat)
Operating temperaturePermissible temperature range
Single Nivotester: –20+60 °C, +50 °C in protective housing
2 or more Nivotesters: –20+50 °C, +40 °C in protective
housing
Storage: –25+80 °C
ElectricalTerminals: removable, 1x6-pole, 1x7-pole
Protection: IP 20
Wire cross-section: 1 x 0.5 mm
2
to 1 x 2.5 mm
2
or
2 x 0.5 mm
2
to 2 x 1.5 mm
2
Without terminals: Flat plug 0.8 x 6.3 as per DIN 46 244
Power supply: supplied according to order specification
200 V240 V 50/60 Hz +15%-10%
100 V127 V 50/60 Hz +15%-10%
42 V48 V 50/60 Hz ±15%
24 V 50/60 Hz ±15%
20 V30 V DC
Isolation:
Transformer between power supply and evaluation circuit
Relay between evaluation circuit and output circuit
Probe capacitance: see Table 3
RelayOutput signal: via potential-free change-over contact, selectable
maximum or minimum fail-safe mode
Max. switching capacity: 250 V AC, 6 A, 1500 VA, cos ϕ = 1,
750 VA, cos ϕ ≥ 0.7
250 V DC, 6 A, 200 W
Response time: 0.2 s, for FTC 421 adjustable 020 s
Short-out time on power failure: approx. 0.3 s
Relay switching staus: Red LED lights when relay de-energised
Operational status: Green LED lights when operational
EMCElectromagnetic compatibility (EMC):
Immunity to EN 50082-1.
Emission to EN 50081-1.
Subject to change without prior notification