Calibration with a covered probe
This calibration is possible with a fully insulated probe or isolating
product only.
Cover the probe to the required switch point.
Capacitance range seekingFind the operational range by proceding as described in
»Capacitance range seeking« on Page 32.
Calibration for minimum
fail-safe mode
If there is no bridge between terminals 12 and 13 of the Nivotester.
Step Procedure
1 Turn the adjuster switch back to zero.
2 Slowly turn the switch clockwise until the red LED lights.
3 When the exact switching position has been found, turn
the adjuster back a half-division.
4 When adjusted, check that the unit is functioning correctly
by filling or emptying the vessel.
Procedure:
Calibration for minimum
fail-safe mode with covered
probe
Calibration for maximum
fail-safe mode
If there is a bridge between terminals 12 and 13 of the Nivotester.
Step Procedure
1 Turn the adjuster switch back to zero.
2 Slowly turn the switch clockwise until the red LED goes out.
3 When the exact switch position has been found, turn the
adjuster back a half-division.
4 When adjusted, check that the unit is functioning correctly
by filling or emptying the vessel.
Procedure:
Calibration for maximum
fail-safe mode with covered
probe
Calibration with a variable level
If it is possible to vary the level, you can also calibrate as follows:
Step Procedure
1 Find the capacitance range as described on Page 32
2 Find the exact switch point with the probe uncovered as
described on Page 32.
- Note the value of the adjuster.
3 Find the exact switch point with the probe covered as
described on Page 33 above.
- Note the value.
4 Set the adjuster to the average of the two values.
5 When adjusted, check that the unit is functioning correctly
by filling or emptying the vessel..
Procedure:
Calibration with a variable level
Calibration
33