2.8 Post-installation check
Is the measuring device damaged (visual inspection)?
Does the device correspond to specifications at the measuring point, including process
temperature and pressure, ambient temperature, minimum fluid conductivity, measuring
range, etc.?
Does the arrow on the sensor nameplate match the actual direction of flow through the pipe?
Is the position of the measuring electrode plane correct?
Were all screws tightened to the specified torques when the sensor was installed?
Were the correct seals used (type, material, installation)?
Are the measuring point number and labeling correct (visual inspection)?
Were the inlet and outlet runs respected?
Inlet run 5 × DN
Outlet run 2 × DN
Is the measuring device protected against moisture and direct sunlight?
Is the sensor adequately protected against vibration (attachment, support)?
Acceleration up to 2 g by analogy with IEC 600 68-2-8
Q-Pulse Id
Active 30/09/2014
Page 33 of 52
Vendor Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instructions
Q-Pulse Id VM454