System integration Proline Promag W 400
58 Endress+Hauser
Designation Description (format) Byte Bit Value
12. Control totalizer 2 (integer) 9…10 0…8 See totalizer 1
13. Not used 11…12 0…8 –
14. Control totalizer 3 (integer) 13…14 0…8 See totalizer 1
15. Not used 15…16 0…8 –
16. External pressure (real) 17…20 0…8 Data format:
Byte 1 to 4: External pressure
Floating-point number
(IEEE754)
17. External pressure unit (integer) 21…22 0…8 • 2165: Pa a
• 2116: kPa a
• 2137: MPa a
• 4871: bar a
• 2166: Pa g
• 2117: kPa a
• 2138: MPa a
• 2053: bar g
• 2182: Psi a
• 2183: Psi g
• 2244: Customer-specific
18. Not used 23…24 0…8 –
19. External reference density (real) 25…28 0…8 Data format:
Byte 1 to 4: External ref. density
Floating-point number
(IEEE754)
20. External reference density unit
(integer)
29…30 0…8 • 2112: kg/Nm
3
• 2113: kg/Nl
• 2092: g/Scm
3
• 2114: kg/Scm
3
• 2181: lb/Sft
3
21. Not used 31…32 0…8 –
22. External temperature (real) 33…36 0…8 Data format:
Byte 1 to 4: External temperature
Floating-point number
(IEEE754)
23. External temperature unit
(integer)
37…38 0…8 • 4608: °C
• 4609: °F
• 4610: K
• 4611: °R
24. Not used 39…40 0…8 –
25. Start verification (integer) 41…42 0…8 • 32378: Start
• 32713: Cancel
26. Not used 43…64 0…8 –