Operation Proline Prosonic Flow B 200 HART
104 Endress+Hauser
Parameter overview with brief description
Parameter Prerequsite Description Selection / User
entry
Factory setting
Assign channel 1 to 4 The Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Assign process variable to
logging channel.
• Off
• Volume flow
• Corrected volume
flow
• Corrected methane
volume flow
• Mass flow
• Energy flow
• Methane fraction
• Calorific value
• Wobbe index
• Temperature
• Sound velocity
• Flow velocity
• Acceptance rate
• Signal asymmetry
• Turbulence
• Signal strength
• Signal to noise
ratio
• Current output 1
Off
Logging interval The Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Define the logging interval for
data logging. This value
defines the time interval
between the individual data
points in the memory.
1.0 to 3 600.0 s 10.0 s
Clear logging data The Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Clear the entire logging data. • Cancel
• Clear data
Cancel