System integration Proline Prosonic Flow B 200 HART
52 Endress+Hauser
9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version 01.02.zz • On the title page of the Operating instructions
• On transmitter nameplate
• Firmware version parameter parameter
"Diagnostics" menu → Device information
→ Firmware version
Release date of firmware version 07.2015 ---
Manufacturer ID 0x11 Manufacturer ID parameter parameter
"Diagnostics" menu → Device information
→ Manufacturer ID
Device type ID 0x5A Device type parameter parameter
"Diagnostics" menu → Device information → Device
type
HART protocol revision 7 ---
Device revision 2 • On transmitter nameplate
• Device revision parameter parameter
"Diagnostics" menu → Device information → Device
revision
9.1.2 Operating tools
Operating tool via
HART protocol
Sources for obtaining device descriptions
• Field Xpert SFX350
• Field Xpert SFX370
Use update function of handheld terminal
FieldCare • www.endress.com → Download Area
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
www.endress.com → Download Area
SIMATIC PDM
(Siemens)
www.endress.com → Download Area
Field Communicator 475
(Emerson Process Management)
Use update function of handheld terminal
9.2 Measured variables via HART protocol
The following measured variables (HART device variables) are assigned to the dynamic
variables at the factory:
Dynamic variables Measured variables
(HART device variables)
Primary dynamic variable (PV) Volume flow
Secondary dynamic variable (SV) Totalizer 1
Tertiary dynamic variable (TV) None
Quaternary dynamic variable (QV) None