Proline Prosonic Flow B 200 HART Commissioning
Endress+Hauser 95
parameters automatically after 60 s if the user skips back to the operational display mode
from the navigation and editing view.
If write access is activated via access code, it can be also be deactivated only via the
access code →  46.
The user role with which the user is currently logged on via the local display
→  46 is indicated by the Access status display parameter. Navigation path:
"Operation" menu → Access status display
Parameters which can always be modified via the local display
Certain parameters that do not affect the measurement are excepted from write protection
via the local display. Despite the defined access code, these parameters can always be
modified even if the other parameters are locked.
Parameters for configuring
the local display
Parameters for configuring
the totalizer
Language Format display Control Totalizer
Contrast display Preset value
Display interval Reset all totalizers
10.8.2 Write protection via write protection switch
Unlike write protection via a user-specific access code, this allows write access to the entire
operating menu - other than the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter):
Via local display
Via service interface (CDI)
Via HART protocol
+
E
3 mm
XXXXXXXXXXXXX
WPCDI
ON
OFF
A0025794
1. Loosen the securing clamp.
2. Unscrew the electronics compartment cover.