Installation Proline Prowirl R 200
18 Endress+Hauser
The pressure loss for flow conditioners is calculated as follows: ∆ p [mbar] = 0.0085 ⋅ ρ
[kg/m
3
] ⋅ v
2
[m/s]
Example for steam Example for H
2
O condensate (
80 °C)
p = 10 bar abs ρ = 965 kg/m
3
t = 240 °C → ρ = 4.39 kg/m
3
v =2.5 m/s
v =40 m/s ∆ p = 0.0085 ⋅ 965 ⋅ 2.5
2
= 51.3 mbar
∆ p = 0.0085 ⋅ 4.394.39 ⋅ 40
2
= 59.7 mbar
ρ : density of the process medium
v: average flow velocity
Installation for delta heat measurements
Order code for "Sensor version", option 3 "Mass flow (integrated temperature
measurement)"
The second temperature measurement is taken using a separate temperature sensor.
The measuring device reads in this value via a communication interface.
In the case of saturated steam delta heat measurements, the Prowirl 200 must be
installed on the steam side.
In the case of water delta heat measurements, the Prowirl 200 can be installed on
the cold or warm side.