Electrical connection Proline Prowirl R 200
26 Endress+Hauser
7.1.3 Terminal assignment
Transmitter
Connection versions
4
+
1
2
+
3
1
2
4
6
+
5
3
A0020738
+
1
2
4
+
3
6
+
5
3
1
2
4
A0020739
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
Terminals 1 to 4:
With integrated overvoltage protection
Terminals 5 to 6:
Without integrated overvoltage protection
1
2
3
4
Output 1 (passive): supply voltage and signal transmission
Output 2 (passive): supply voltage and signal transmission
Input (passive): supply voltage and signal transmission
Ground terminal for cable shield
Order code for "Output" Terminal numbers
Output 1 Output 2 Input
1 (+) 2 (-) 3 (+) 4 (-) 5 (+) 6 (-)
Option A 4-20 mA HART (passive) - -
Option B
1)
4-20 mA HART (passive) Pulse/frequency/switch
output (passive)
-
Option C
1)
4-20 mA HART (passive) 4-20 mA (passive) -
Option D
1)
4-20 mA HART (passive) Pulse/frequency/switch
output (passive)
4-20 mA current input
(passive)
Option G
2)
PROFIBUS PA Pulse/frequency/switch
output (passive)
-
1) Output 1 must always be used; output 2 is optional.
2)
PROFIBUS PA with integrated reverse polarity protection.
Remote version
In the case of the remote version, the sensor and transmitter are mounted separately
from one another and connected by a connecting cable. The sensor is connected via the

Other manuals for Endress+Hauser Proline Prowirl R 200