Conversion transmitter Promag 50/53 W, P, H to Promag 55 remote version
Endress + Hauser 7
I List of Parameter Promag 50, Promag 55 J Settings depending on mains frequency
The integration time must be parameterized in the following way:
For 50 Hz main frequency or DC: 20 ms integration time.
For 60 Hz main frequencyz: 16,7 ms integration time.
The integration time is only adjustable by the service.
Promag 50 Promag 55
Parameter to select
Current Parameter
Value
Parameter to enter
Parameter-
No.
System-Units:
Unit Volume flow Unit Volume flow 0402
Unit Volume Unit Volume 0403
Operation
Language Language 2000
Private Code Private Code 2021
User Interface:
Format Format 2202
2402
2602
Contrast LCD Contrast LCD 2003
Totalizer:
Sum Sum 3040
Overflow Overflow 3041
Current Output:
Current span Current span 4001
Value 20mA Value 20mA 4003
Time Constant Time Constant 4005
Measuring Mode:
Operation Mode Operation Mode 4200
Pulse Value Pulse Value 4222
Pulse Width Pulse Width 4223
Outputsignal Outputsignal 4226
Assign Status
Output
Assign Status 4241
On-Value On-Value 4242
Off-Value Off-Value 4244
Communication:
Tag Name Tag Name 6000
Tag Describtion Tag Describtion 6001
Bus-Adress Bus-Adress 6002
Write Protection Write Protection 6004
Manufactorer ID Manufactorer ID 6040
Device ID Device ID 6041
Process Parameters:
On-Value Low Flow
Cut Off
On-Value Low Flow
Cut Off
6402
EPD EPD 6420
System Parameters:
Installation
Direction Sensor
Installation Direction
Sensor
6606
Measuring Mode Measuring Mode 4004
4206
4225
4705
Positive Zero Return Positive Zero Return 6605
System Damping System Damping 6603
- already parameterized Integration Time 6604
Sensor data:
K-Factor already parameterized K-Faktor positive
K-Faktor negative
6801
6802
Zero Point already parameterizedt Zero Point 6803
Nominal Diameter already parameterized Nominal Diameter 6804
Measuring Period already parameterized Measuring Period 6820
EPD-Electrode already parameterized EPD-Electrode 6822
Supervision:
Simulation Failsafe
Mode
Simulation Failsafe
Mode
4006
4209
4227
Alarm Delay Alarm Delay 8005
Sensor Version:
Serial-Number Serial-Number 8200
Sensor Type Sensor Type 8201
Promag 55W, 55P Promag 55H
DN
[mm]
DN
[inch]
Measuring Period
[ms]
DN
[mm]
DN
[inch]
Measuring Period
[ms]
50 Hz 60 Hz 50 Hz 60 Hz
25 1" 60 50 2
1
/
12
" 40 33,3
32 – 60 50 4
5
/
32
" 40 33,3
40 1
1
/
2
"60 50 8
5
/
16
" 40 33,3
50 2" 60 50 15
1
/
2
" 40 33,3
65 – 60 50 25 1" 40 33,3
80 3" 60 66,7 25 DIN – 40 50,0
100 4" 60 66,7 40 1
1
/
2
" 60 50,0
125 – 100 100 50 2" 60 50,0
150 6" 100 100 65 2
1
/
2
" 60 50,0
200 8" 100 100 80 3" 60 66,7
250 10" 120 116,7 100 4" 60 66,7
300 12" 120 116,7
350 14" 120 116,7
400 16" 120 116,7
450 18" 140 150
500 20" 140 150
600 24" 160 166,7