Prosonic S FMU90 Flow Measurement PROFIBUS Commissioning
Endress+Hauser 39
4 Beta Specify the value of the parameter β,
(only available for "type" = "formula")
Gamma Specify the value of the parameter γ,
(only available for "type" = "formula")
C Specify the value of the parameter C,
(only available for "type" = "formula")
Max. flow Specify the maximum flow of the flume or weir,
(not available for "type" = "table")
Details ä 42 "max flow"
5 Flow N empty
calibration
(N = 1 or 2)
Empty E Specify the distance E between the reference point of the
sensor and the zero of the measurement. The zero is
the bottom of the weir or
the lowest point of the weir crest
Blocking distance Indicates the blocking distance of the respective sensor; the
maximum level may not project into the blocking distance.
6 Flow N
(N = 1 or 2)
Flow N
(N = 1 or 2)
Displays the currently measured flow
(for checking purposes)
Level Displays the currently measured level
(for checking purposes)
Distance Displays the currently measured distance between the
reference point of the sensor and the liquid surface
(for checking purposes)
7 Flow N check value
(N = 1 or 2)
Distance Displays the currently measured distance between the
reference point of the sensor and the liquid surface.
Check distance Compare the displayed distance with the real value:
"Distance = ok" "flow N mapping"
"Distance too small" "flow N mapping"
"Distance too big" basic setup completed
"Distance unknown" basic setup completed
"Manual" "flow N mapping"
8 Flow N mapping
(N = 1 or 2)
Distance Displays the currently measured distance between the
reference point of the sensor and the liquid surface
Range of
mapping
Determines the range over which the mapping is recorded;
confirm the predefined value or enter your own value.
Start mapping Select:
No: the mapping is not recorded
Yes: the mapping is recorded; after completion, the "flow
N state" function appears (see below)
Step Parameter Set Parameter Remarks