Prosonic T FMU30
10 Endress+Hauser
Installation conditions for
level measurements
L00-FMU30xxx-17-00-00-xx-005
Do not install the sensor in the middle of the tank (3). We recommend leaving a distance between the sensor
and the tank wall (1) measuring 1/6 of the tank diameter.
Protect the device against direct sun or rain (2) ä 26 "Weather protection cover".
Avoid measurements through the filling curtain (4).
For solid application where bulk solid cones appear, align the sensor membrane perpendicular to the surface.
Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not located within the
emitting angle . In particular, symmetrical equipment (6) such as heating coils, baffles etc. can influence
measurement.
Never install two ultrasonic measuring devices in a tank, as the two signals may affect each other.
To estimate the detection range, use the 3 dB emitting angle .
Installation in narrow shafts
1
234
5
6
1/6D
D
r
a
L
Sensor L
max
r
max
1½" 11° 5 m (16 ft) 0.48 m (1.6 ft)
2" 11° 8 m (26 ft) 0.77 m (2.5 ft)
In narrow shafts with strong interference echoes, we
recommend using an ultrasound guide pipe (e.g. PE
or PVC wastewater pipe) with a minimum diameter
of 100 mm (3.94 in).
Make sure that the pipe is not soiled by accumulated
dirt. If necessary, clean the pipe at regular intervals.
L00-FMU30xxx-17-00-00-xx-010