Prosonic T FMU30
6 Endress+Hauser
L00-FMU3xxxx-05-00-00-xx-100
1Sensor 2"
2Sensor 1½"
A Attenuation (dB)
R Range (m)
Example
These measuring conditions have been taken into account during the calculation of the maximum measuring
range in solid applications.
Operating frequency
Output
Output signal 4 to 20 mA
Signal on alarm Error information can be accessed via the following interfaces:
On-site display (error symbol, error code and plain text description)
Current output, signal on error can be selected (e.g. according to NAMUR recommendation NE43)
Output damping Freely selectable, 0 to 255 s
Linearization The linearization function of the instrument allows conversion of the measured value into any unit of length
or volume. In open channels or measuring weirs, also a flow linearization is possible (calculation of the flow
from the measured level).
The linearization table for calculating the volume in an horizontal cylindrical tank is preprogrammed. You can
also enter any number of other tables containing up to 32 value pairs either manually or semi-automatically (by
filling the vessel under controlled conditions).
10 20 30 40 50 60 70 80
1
5
10
A [dB]
R [m]
1
2
Strong turbulence surface approx. 50 dB
•No dust formation 0 dB
Filling curtain in
detection range 10 dB
Temperature diff. < 20 °C (68 °F) 0 dB
approx. 50 dB range approx. 3.5 m (11 ft) for FMU30 2" sensor
1½" sensor 2" sensor
approx. 70 kHz approx. 50 kHz