Installation Prosonic T
12 Endress+Hauser
3.3.2 Installation in narrow shafts
3.3.3 Installation conditions for flow measurements
Install the device at the inflow side (B), as close above the maximum water level H
max
as possible
(take into account the blocking distance BD).
Position the instrument in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
Example: Khafagi-Venturi flume
A0019607
A Khafagi-Venturi flume BD Blocking distance
B Inflow E Empty calibration
C Outflow F Full calibration
V Direction of flow
In narrow shafts with strong interference
echoes, we recommend using an ultrasound
guide pipe (e.g. PE or PVC wastewater pipe)
with a minimum diameter of 100 mm (3.94 in).
Make sure that the pipe is not soiled by accumu-
lated dirt. If necessary, clean the pipe at regular
intervals.
L00-FMU30xxx-17-00-00-xx-010
1 Venting hole
1
1 x b
0
b
0
BD
A
E
BC
V
H
max
=F