RIA15 Commissioning
Endress+Hauser 35
Setup menu (SETUP)
Parameters Values visible at Description
UNIT %
°C
°F
K
USER
MODE =
4-20
Use this function to select the unit for displaying the
value. If "USER" is selected, a user-defined unit can be
entered in the TEXT parameter.
TEXT Customized text,
5-digit
MODE =
4-20
User-defined unit, only visible if the "USER" option has
been selected under UNIT.
SCAN NO
YES
MODE =
HART
Select "YES" to start scanning. All addresses are then
automatically scanned once in a HART® application until
a sensor/actor is found. Scanning runs from 0 to 63. Only
addresses up to 15 are permitted for HART 5. Once the
address of the sensor/actor whose values are to be
displayed is found, the address must be confirmed by
pressing the 'E' key. This address is adopted and is used
even after a device restart.
By pressing the '+' or '–' key, it is possible to search for
other addresses.
Pressing '+'- and '-' simultaneously will cancel scanning.
If "NO" is selected, scanning is not active. The address of
the sensor/actor, whose values are to be displayed on the
process display unit, must be configured manually using
the operating keys.
ADDR Numerical value
0 to 63
Default: 0
MODE =
HART
Use this function to enter manually the address of the
HART® sensor/actor whose values are to be displayed.
If the address of the HART® slave is changed, it
must also be changed on the process display unit.
To do this, either enter the address manually or
search using SCAN mode.
MTYPE PRIM
SEC
MODE =
HART
Use this function to select the HART® master type:
PRIM = Primary master
SEC = Secondary master
HART1-HART4 MODE =
HART
Use this function to select which HART® value of a
sensor/actor (PV, SV, TV, QV) should be activated and
configured:
HART1 = PV
HART2 = SV
HART3 = TV
HART4 = QV
Press the E key to open the configuration submenu.
DISP1 –DISP4 OFF
MAN
AUTO
MODE =
HART
Use this function to select how or whether the value
should be displayed.
OFF: Value is not displayed
MAN: You can manually scroll through activated HART®
values by pressing '+' or '–'. Otherwise the values are not
displayed. If all four HART® values (HART1 to HART4)
are set to "MAN", HART1 (PV) is displayed if you do not
scroll manually through the values.
AUTO: Activated HART® values are shown alternately
(switching time can be configured in the EXPRT menu
under "TOGTM"). If one value is set to AUTO, this value is
displayed continuously on the device.
For the "Level" option for FMR20: default for DISP3 and
DISP4 = OFF
DEC1 – DEC4 0 DEC
1 DEC
2 DEC
3 DEC
4 DEC
MODE =
HART
Number of decimal places