Soliwave FDR56/FQR56
Endress+Hauser 13
Mounting
4.2.2 Mounting without contact with the process
• Risk of condensate formation on the inner process wall → plug 2
• A minimize → minimize signal attenuation
• Observe maximum temperature T → 10
1 2
D
A
T
0000000191
8 Mountinginfrontofmicrowave-impermeableprocesswall
1 Microwave-permeableplug
2 Microwave-permeableplugincaseofcondensateformationontheinnerprocesswall
4.2.3 Mounting with accessories
→ BA01684F
Observe the enclosed instructions enclosed with the accessories!
4.3 Post-installation check
Is the device undamaged (visual inspection)?
Does the device conform to the measuring point specications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
Are the measuring point number and labeling correct (visual inspection)?
Is the device adequately protected against precipitation and direct sunlight?
Is the device properly secured?