Soliwave FDR56/FQR56
Endress+Hauser 23
Commissioning
Move the encoding switch to the initial position 0
→ Display of the current signal strength
• The Soliwave microwave barrier is adjusted, if with free or minimum covered path a) on
devices with switching output the switching point (LED 5) is exceeded safely or b) on devices
with current output a minimum of 6 LEDs are lit (ideally all 10 LEDs are lit).
• A repeated automatic adjustment (function 1 or function 2) resets any adjustment carried
out earlier.
7.3 Advanced settings
7.3.1 Hysteresis (Function 5)
A hysteresis from 1 to 4 LEDs can be programmed for the switch output (change-over contact
with relay, normally open contact with solid-state relay, of no signicance for current output).
The xed switch point with increasing signal strength is at the transition from LED 5 to LED 6.
For decreasing signal strength, the switch point can be congured between the transition
from LED 5 to LED 4 (minimum hysteresis of an LED) and maximum between LED 2 to LED 1
(maximum hysteresis of four LEDs).
H
H
H = 1
H = 4
0000000275
14 Adjustmentoftheswitchinghysteresis
H Hysteresis
Move the encoding switch to position 5
→ Display of the function number
→ Aer 2 seconds: Display of the congured hysteresis, example:
Press the operation buttons on the device in order to congure the hysteresis in the range
from 1 to 4 LEDs
→ Display of the changed hysteresis, example hysteresis increased from 3 LEDs to 4 LEDs: