Soliwave FDR56/FQR56
28 Endress+Hauser
Commissioning
7.4 Reset to factory settings (function F)
This function can be used to reset the FDR56 to its factory settings as follows:
Move the encoding switch to position F
→ Display of the function number
→ All LEDs go out aer 2 seconds.
Press both buttons on the device to set it to the factory defaults
→ All LEDs illuminate as conrmation.
Move the encoding switch to the initial position 0
→ Display of the current signal strength
7.5 Simulation
The FDR56 gives you the ability to simulate a signal and thereby an output variable, indepen-
dent of the process, for example, in order to congure a downstream PLC or a data logger.
The simulation is carried out as follows (function 6 = standard setting):
Move the encoding switch to position 9
→ Display of the function number
→ Aer 2 seconds: Display of the simulated signal strength, example: signal strength = 0
LEDs, switch output: not switched, current output: 4 mA
Press the button on the device to congure the desired signal strength
→ Display of the changed simulated signal strength, example: signal strength = 8 LEDs,
switch output: switched, current output: 16.8 mA
Move the encoding switch to the initial position 0
→ Display of the current signal strength
The simulation ends as soon as the encoding switch is no longer at position 9.