Soliwave FDR56/FQR56
20 Endress+Hauser
Commissioning
Setting the selected function
→ The two operating buttons can be used to increase/decrease the value or to switch the
selection.
Example: Function 3 (manual adjustment on free path)
oder
→ →
→
→
... ...
The congured value is stored as soon as the function is switched.
→ The value can be displayed again at any time by selecting the corresponding parameter
conguration function and changed if necessary.
Aer the parameterization has been completed (i.e. aer the microwave barrier has been
adapted to the respective medium), the encoding switch must be returned to the "0" posi-
tion and the FDR56 is now ready for operation.
• The device is in operating mode in encoding switch position "0" only. All other positions are
for parameter conguration.
• In parameterization mode, the microwave barrier continues to operate in the background,
and changed settings are taken into account directly.
• Aer completing the settings, set the encoding switch back to the initial position "0" (=
operation).
6.3 Operation of the FQR56
Selection of the switch position 0 to 4 (slightly dierent operating frequency in each case)
→
E
A
9
6
2
1
...
F
E
A
6
2
1
Select the next switch position if the interference is still present.
The switch positions 5 to F have no function, the operating frequency in these positions
corresponds to switch position 0.
7 Commissioning
The microwave barrier is ready for operation a maximum of 3s aer the supply voltage is
applied.
7.1 Function check
Function check
• "Post-installation check" checklist
• "Post-connection check" checklist