Soliwave FDR56/FQR56
Endress+Hauser 27
Commissioning
The delays impact only the switch outputs (relay and solid-state relay); they have no signi-
cance for the current output.
If the process conditions are unstable, the signal strength can be calmed with a parameteriz-
able damping (function A).
7.3.4 Damping (function A)
For unstable process conditions, the display of the signal strength can be stabilized by a con-
gurable damping; averaging of the output signal takes place here over the set time.
Setting Damping Setting Damping
Without 2s
100ms 3s
200ms 5s
300ms 10s
500ms 20s
1s
Move the encoding switch to position A
Display of the function number
Aer 2 seconds: Display of the congured damping, example damping = 200ms:
Press the button on the device to congure the damping
Display of the changed damping, example damping increased to 500ms
Move the encoding switch to the initial position 0
Display of the current signal strength
The set time not only damps the signal strength display, but also impacts the switch output
(for example, a delayed switching) and the current output (rises/falls with a delay).
If only the switch output is to be stabilized, it is advisable to congure a switch-on and/or o
delay. → 25
The switch-on and/or o delay and damping can be combined, which causes the detection
to be signicantly slower.