Soliwave FDR56/FQR56
26 Endress+Hauser
Commissioning
t(T) t(T) t(S) t(S)
0000000213
16 Adjustmentofswitchingdelays
t(S) Switch-ondelay(function7)
t(T) Switch-offdelay(function8)
Setting Delay t(S), t(T) Setting Delay t(S), t(T)
Without 2s
100ms 3s
200ms 5s
300ms 10s
500ms 20s
1s
Move the encoding switch to position 7 (switch-on delay t(S)) or position 8 (switch-o
delay t(T))
Display of the function number, switch-o delay example
Aer 2 seconds: Display of the congured delay time, example switch-o delay = o:
Press the button on the device to congure the delay time
Display of the changed delay time, example switch-o delay = 300ms:
Move the encoding switch to the initial position 0
Display of the current signal strength