Soliwave FDR56/FQR56
24 Endress+Hauser
Commissioning
Move the encoding switch to the initial position 0
Display of the current signal strength
A larger hysteresis can also be used to prevent the output from continuously switching with
a uctuating signal strength. If, for example, the signal strength continuously uctuates
between the third and eighth LED, the factory default hysteresis of an LED would lead to the
switch output continuously switching when the fourth LED is undershot.
This setting has no signicance for the current output.
7.3.2 Limit signal function (function 6)
For devices with a relay and solid-state relay, the limit signal function determines the swit-
ching behavior upon exceeding and undershooting the limit value (upper limit value LED 5,
lower limit determined by hysteresis).
A
A
B
C
0000000295
15 Adjustmentoflimitsignalfunction
A Restposition(supplyvoltagemissing)
B Minimumsafety
C Maximumsafety(defaultsetting)
Move the encoding switch to position 6
Display of the function number
Aer 2 seconds: Display of the congured limit signal function, example:
Press the button on the device in order to change between the two possible limit signal
functions
Display of the changed limit signal function, example:
Move the encoding switch to the initial position 0
Display of the current signal strength