37Installation instructions
EN
Unit
Hydronic (water)
after-heating coil
(LxDxH)
Duct connection
Ø mm
Hydronic (brine)
cooling coil
(LxDxH)
Duct connection
Ø mm
Right hand
/ left hand
change
Condensate drain
connection
External sensors
LTR-3 eWind W VEAB CWW
160-3-2,5
276x313x255 mm
Ø 160 mm
No No TE10 supply air sensor
TE45 return water sensor
LTR-4 eWind
E-CHG
VEAB CWK
200-3-2,5-L/R
395x415x330 mm
Ø 200 mm
Yes Yes
G ½” external thread
TE01 outside air sensor
LTR-6 eWind
E-CHG
VEAB CWK
250-3-2,5-L/R
395x491x405 mm
Ø 250mm
Yes Yes
G ½” external thread
TE01 outside air sensor
LTR-7-eWind
E-CG
VEAB CWK
250-3-2,5-L/R
395x491x405mm
Ø 250mm
Yes Yes
G ½” external thread
TE10 supply air sensor
LTR-7-eWind
E-CHG
VEAB CWK
400-3-2,5-L/R
450x715x529 mm
Ø 400mm
Yes Yes
G ½” external thread
TE01 outside air sensor
LTR-7-XL eWind
E-CG
VEAB CWK 315-3-
2,5 276x560x504
mm Ø 400mm
No Yes
G ½” external thread
TE10 supply air sensor (CG)
LTR-7-XL eWind
E-CHG
VEAB CWK
400-3-2,5-L/R
450x715x529 mm
Ø 400mm
Yes Yes
G ½” external thread
TE01 outside air sensor (CHG)
CHG Pre-heating and pre-cooling coils
These coils are installed in the outside air duct (before the ventilation unit).
Denition CHG 200 CHG 250 CHG 400
Coil type VEAB CWK 200-3-2,5-L/R VEAB CWK 250-3-2,5-L/R VEAB CWK 400-3-2,5-L/R
Product code.
L: K930040501V (left)
R: K930040501 (right)
L: K930040502V (left)
R: K930040502 (right)
L: K930040503V (left)
R: K930040503 (right)
Suits listed Enervent units
(NOTE It is possible to use a
bigger coils than listed here)
Pinion, Pingvin, Pingvin XL,
Pandion, LTR-2, LTR-3, LTR-4
Pelican, LTR-6 Pegasos, LTR-7
Coil duct connection. Ø 200 mm Ø 250 mm Ø 400 mm
Coil outer dimensions and
weight dry/with uid.
L 395 x H 330 x D 415 mm,
10/11 kg
L 395 x H 405 x D 491 mm,
12/13,5 kg
L 450 x H 529 x D 715 mm,
22/24,7 kg
Filter (plain lter)
1 pcs, ltering class G3.
379 x 296 x 13 mm
Spare lter package, 6 pcs
lters (no mesh).
1 pcs, ltering class G3
454 x 372 x 13 mm
Spare lter package, 6 pcs
lters (no mesh).
1 pcs, ltering class G3
679 x 472 x 13 mm
Spare lter package, 6 pcs
lters (no mesh).
Fluid pipe connections
Condense water drain
(underpressure)
22 mm
½ ”, must be equipped with
water trap.
22 mm
½ ”, must be equipped with
water trap.
22mm
½ ”, must be equipped with
water trap.
Valve and valve actuator.
Belimo ”R313” (R3015-4-S1),
3-way, kvs 4, DN 15
TR24-SR, 0-10V
Belimo ”R317” (R3020-4-S2),
3-way, kvs 4, DN 20
HRYD24-SR, 0-10V
Belimo ”R322” (R3025-6P3-S2),
3-way, kvs 6,3, DN 25
HRYD24-SR, 0-10V
Additional outside air sensor 1 pcs 5 m sensor 1 pcs 5 m sensor 1 pcs 5 m sensor