45Installation instructions
EN
PINION, PINGVIN, PINGVIN XL, PANDION, PELICAN, PEGASOS, PEGASOS XL
UNIT PINION PINGVIN PINGVIN XL PANDION PELICAN PEGASOS PEGASOS XL
E-models
Power of standard
electrical
afterheater coil
800 W 400 W 800 W 800 W 2 000 W 4 000 W 4 000 W
Power of optional
electrical
afterheater coil
- 800 W - - 4 000 W 6 000 W 6 000 W
Mains supply 230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
16 A
400 V 3~/
50 Hz
3x16 A
400 V 3~/
50 Hz
3x16 A
W-models
Hydronic
afterheater
location
In duct In duct In duct Built-in Built-in Built-in Built-in
35/25°C total coil
power
1,2 kW* 1,5 kW* 2,5 kW* 2,6 kW - 6,4 kW* 7,7 kW*
30/20°C total coil
power
- 1,3 kW - 2,8 kW* 3,2 kW* - -
60/40°C total coil
power
0.9 kW 2,0 kW 2,7 kW 3,0 kW 3,5 kW 6,2 kW 6,7 kW
Mains supply 230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
230 V~/
50 Hz
10 A
Pipe connection 10 mm 10 mm 10 mm 15 mm 15 mm 28 mm 28 mm
Water ow 0,03 l/s 0,04 l/s 0,03 l/s 0,07 l/s 0,08 l/s 0,15 l/s 0,19 l/s
Water system
pressure loss
4 kPa 10,3 kPa 5,9 kPa 6,6 kPa 9,2 kPa 3,3 kPa 3,3 kPa
Kvs value of valve 0,63 0,63 1,0 1,0 1,6 4,0 4,0
Valve connection
DN
15 15 15 15 15 15 15
Dimensions of
duct coils
(w x h x l) mm
313x255x276
Ø 125 mm
313x255x276
Ø 160 mm
398×330×276
Ø 200 mm
- - - -
CG-models
Cooling (CG) coil
location
- - In duct Built in Built-in Built-in In duct
Total coil power - - 1.2 kW 1.5 kW
(built-in)*
1.2 kW (duct)
1.7 kW 3.2 kW 3.5 kW
Pipe connection - - 22 mm 15 mm
(built-in)*
22 mm (duct)
15 mm 28 mm 22 mm
Brine ow - - 0.06 l/s 0.08 l/s
(built-in)*
0.07 l/s (duct)
0.09 l/s 0.16 l/s 0.17 l/s
Water system
pressure loss
- - 7.9 kPa 1.5 kPa
(built-in)*
7.7 kPa (duct)
2.0 kPa 3.4 kPa 8.5 kPa
Kvs value of valve - - 2.6 1.6 4.0 4.0 6.3
Valve connection
DN
- - 15 15 15 20 25
Dimensions of
duct coil (w x h x
l) mm
- - 415×330×395
Ø 200 mm
415x330x395
Ø 200 mm
- - 560x504x276
Ø 315 mm