3.g.6 Return Factory Settings (P5.6)
The below parameters marked with are returned to the “default (factory)” values.
MENU
INDEX
PARAMETERS
Default Setting
Minimum Value
Maximum
Value
Return to Factory Settings
User Parameters
P3.1
Operating Mode
Automatic
Continuous
Automatic
P3.2
Pressure Unload
7.5 Bar
5.0 Bar
15.6 Bar
P3.3
Wait on Unload
180 sec.
10 sec.
1200 sec.
P3.4
Pressure Load
6.0 Bar
3.5 Bar
15.4 Bar
P3.5
To Stop Delay
15 seconds
5 seconds
30 seconds
P3.6
Pressure Unit
Bar
Bar
PSI
P3.7
Temperature Unit
Celsius
Celsius
Fahrenheit
P3.8
To Start Delay
5 seconds
0 seconds
60 seconds
P3.9
Dryer Time
30 min.
1 min
50 min.
P3.10
User Password
1234
0000
9999
SERVICE PARAMETERS
Pressure Parameters
P4.1.1
Stop Pressure
8.0 Bar
0.0 Bar
16.0 Bar
P4.1.2
Alarm Pressure
7.8 Bar
0.0 Bar
16.0 Bar
P4.1.3
Screw Pressure Warning
7.8 Bar
0.0 Bar
16.0 Bar
P4.1.4
Screw Pressure Alarm
8.0 Bar
0.0 Bar
16.0 Bar
P4.1.5
Delta Pressure Warning
2.0 Bar
0.0 Bar
9.0 Bar
P4.1.6
Delta Pressure Alarm
2.3 Bar
0.0 Bar
9.0 Bar
P4.1.7
Delta Pressure Delay
1 sec.
0 sec.
600 sec.
P4.1.8
Screw Pressure Start Value
1.0 Bar
0.0 Bar
3.0 Bar
Temperature Parameters
P4.2.1
Upper Temperature Limit
110 Cel
90 Cel
120 Cel
P4.2.2
Lower Temperature Limit
0 Cel
-10 Cel
10 Cel
P4.2.3
Temperature Alarm
105 Cel
80 Cel
110 Cel
P4.2.4
Loading Temperature
25 Cel
20 Cel
70 Cel
Timing Parameters
P4.3.1
Star / Delta Duration
6 seconds
2 seconds
30 seconds
P4.3.2
Delay for Start
1 seconds
0 seconds
60 seconds
P4.3.3
Reloading
1 seconds
0 seconds
60 seconds
P4.3.4
Auto Run Time
0 seconds
0 seconds
60 seconds
P4.3.5
Air Draining Time
10 seconds
0 seconds
60 seconds
P4.3.6
Max. Starts / Hour
6
0
10
Service Duration
P4.4.1
General Maintenance
2500 hours
0 hours
99999 hours
P4.4.2
Bearing Maintenance
20000 hours
0 hours
99999 hours
P4.4.3
Oil Change
2500 hours
0 hours
99999 hours
P4.4.4
Air Filter
2500 hours
0 hours
99999 hours
P4.4.5
Oil Filter
2500 hours
0 hours
99999 hours
P4.4.6
Separator Filter
5000 hours
0 hours
99999 hours
Communication Parameters
P4.5.1
Load Valve Control Source
Sensor
Sensor
MODBUS
P4.5.2
Start/Stop Control Source
Panel
Panel
MODBUS
P4.5.3
Com. Work Mode
Not Acknowledged
Not Acknowledged
Acknowledged
P4.5.4
Modbus Address
1
1
100
P4.5.5
Baud Rate
19200 bps
2400 bps
19200 bps

Table of Contents