3. Pull out the steam transferring pipe on the humidifying container.
4. Rive the power connecting cables of the main electrode.
5. Pull out the connecting cable of the detector of high water level.
6. Loosen the fixing belt on the humidifying container, and lift up the container to remove
it.
7. Fix the new humidifying container, and connect the steam transferring pipe.
8. Connect the cable between the main electrode and the detector of high water level.
9. Set the humidify switch at the automatic water drainage status, and check it again to
finish the replacement.
Note
The drain pipe of the unit shall not be higher than the water drainage outlet of the
humidifier.