Shenzhen Envicool Technology Co., Ltd.
The indoor unit of the XRow is configured with controller. The controller has Chinese
&English LCD . The LCD is used for parameters setting and displaying temperature and
humidity, system operation, set values and alarm information. The cooling and alarm control
set values can be adjusted through these selection buttons for system operation.
All control set values and alarm set values in the system can be set by program. The
temperature is displayed in Celsius degree on the LCD. Those set values are stored in internal
memory, and will not be lost even when there is any power failure.
For direct expansion (DX) units, the indoor unit is equipped with evaporator coils, electronic
expansion valves, EC fans, drier filters, sight glasses, low pressure pressure sensors,
temperature and humidity sensors, floor leak sensors, and condensate pumps (optional ),
compressor, high pressure switch, exhaust temperature sensor, etc.
XRow series inter-row air conditioners are divided into several airflow organization forms:
back in and front out, back in and front, left and right air out.
The air cooled outdoor unit is installed outside of computer room.The outdoor units include
axial fans, condensing coils, high-pressure pressure sensors, fan speed controllers, etc.
IF pump cabinet is installed outdoors, including liquid reservoir, refrigerant pump,
electrical components, etc.
XRow series air conditioning unit includes the compressor system.The overall layout of the
system is shown in Figure 1-1~Figure 1-2.