FIKE CORPORATION
FM 3020541 Fike Explosion Protection System Page 19 of 32
P/N E06-051 Rev. 8 10/06
Exhibit 5-8 Configuration Table for Explosion Protection Controller
Filter
Setting
(msec)
1
1
1
1
1
1
1
1
Detection Circuit 3
Enabled
---- Software ----
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Filter
Setting
(msec)
1
1
1
1
5
5
5
5
Threshold
Activation
Pressure
(psi)
0.50
0.75
1.00
1.50
0.50
0.75
1.00
1.50
Detection Circuit 2
Warning
Pressure
(psi)
---- User Selectable with Software ----
0.25
0.30
0.50
1.00
0.25
0.30
0.50
1.00
Filter
Setting
(msec)
1
1
1
1
5
5
5
5
Threshold
Activation
Pressure
(psi)
0.50
0.75
1.00
1.50
0.50
0.75
1.00
1.50
Detection Circuit 1
Warning
Pressure
(psi)
---- User Selectable with Software ----
0.25
0.30
0.50
1.00
0.25
0.30
0.50
1.00
4
Off
Off
Off
Off
Off
Off
Off
Off
On
3
Off
Off
Off
Off
On
On
On
On
Off
2
Off
Off
On
On
Off
Off
On
On
Off
Mode Switch Position
1
Off
On
Off
On
Off
On
Off
On
Off
PC Configure - Used to provide expanded programming options.
Single Detector Release - Any detection circuit will initiate a release sequence from the Explosion Protection Controller
Rate of Rise Operation is Disabled for all Detection Circuits
Operating
Mode
PC Config
SDR
SDR
SDR
SDR
SDR
SDR
SDR
SDR
PC Config
SDR
Config #
0
1
2
3
4
5
6
7
8
Definitions: