FIKE CORPORATION
Page 22 of 32 Fike Explosion Protection System FM 3020541
10/06 P/N E06-051 Rev. 8
7.0 DECOMMISSIONING PROCEDURE / CHECK-LIST
The following procedure must only be performed
by a Fike qualified Service Engineer, who has
been assigned to prepare and complete the
decommissioning of the above referenced
Explosion Protection System.
Each step in the listed procedure must be adhered
to and completion/acceptance of this form is
mandatory. The Service Engineer must check off
each of the following steps. In the case of non-
compliance, the observed discrepancy must be
corrected before completion of the system
decommissioning.
Exhibit 7-1 Decommissioning Steps
STEPS / DESCRIPTION
1. Use Fike system/project component location
diagram to record and verify the locations of
all Fike system components for each zone
and system.
pass fail Remark/
Note No.
2. Control panel to be disarmed/shutdown. pass fail Remark/
Note No.
3. All suppressor/valve actuators to be shunted. pass fail Remark/
Note No.
4. Each suppressor/valve container to be
depressurized.
Note: Do not ventilate nitrogen in a confined
space.
pass fail Remark/
Note No.
5. Power supply to the control panel to be
isolated by the customer and disconnected to
prevent accidental reconnection. Fike to
verify.
pass fail Remark/
Note No.
6. Control panel battery to be disconnected and
removed for proper disposal.
pass fail Remark/
Note No.
7. Each actuator is to be removed and placed in
a storage housing, to be either stored on site
or removed for proper disposal.
pass fail Remark/
Note No.
8. Verify that all suppressor/valve gauges are
reading zero, replace fill valve cap loosely.
pass fail Remark/
Note No.
ATTENTION: SYSTEM IS NOW DECOMMISSIONED AND READY
FOR DISMOUNTING BY THE CUSTOMER.