EasyManua.ls Logo

Esco Class II - Page 56

Esco Class II
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
Problem 7: Light always OFF
Cause Corrective Action
Sash in SASH
ALARM state
Is the Light LED on the front panel ON?
If the light does not turn on, press the Light button and make sure the sash is in the
Normal operating position (Ready Position Normal Operating height).
Note: The sash must be at the Normal Operating position.
Is the cabinet in Warm Up period?
Note: The fluorescent light will not light if the cabinet is in Warm Up period unless
the cabinet is in Quick Start Mode.
Move the sash to Ready position (normal operating height).
Switch on the light by pressing LIGHT button on the membrane.
If the LED is ON the keypad and main board are functioning correctly.
If fluorescent light does not light with the window in the proper position Proceed to
the next step
If the LIGHT LED still does not light, skip to Ready magnetic switch Issues in this
table.
Burned out
fluorescent tube
Replace the faulty fluorescent tube.
Fluorescent tubes are located inside the blue panel.
The white lamp holder can be pulled off from the tubes.
Defective
Fluorescent ballast
or Relay Board
issues
Check incoming voltage to the Relay board.
Locate LS7 circuit and measure AC voltage between BLUE (NEUTRAL) terminal block
and the end terminal (with Red cable) on the three terminal strip (J13 on relay
board).
If there is voltage to the end terminal (Terminal with cable), check the central
terminal (Normally Open Circuit) to the BLUE (NEUTRAL) terminal block.
No voltage at the central terminal indicates a blown fuse or the circuit is not
energized.
Check Fuse F7 on relay board. See Figure 7-1 below.
If fuse F7 is blown, as temporary solution, use F5 (spare) to replace F7.
If fuse F7 is good, check the voltage between the BLUE (NEUTRAL) terminal block
and the end terminal on the LS7 circuit (J13 on relay board).
Voltage at the end terminal with no cable indicates the F7 fuse is good and the
circuit is not energized.
Make sure the LIGHT LED is on.
If the ballast has power and the bulbs are new the problem is either connections or
the ballast.
Check Connector C connections. If there are no lose terminals, replace the ballast.
Ready magnetic
switch Issues
With the LIGHT LED ON and the sash at the Normal operating position (Ready)
Does the Display indicate “SASH: OK” or “SASH: NO!
SASH: NO!” indicates the sash is not at the proper position and the LIGHT LED
should not be on. This indicates a main board problem or a magnetic switch
detection problem.
Figure 7
-
1
F7
LS7

Related product manuals