- Economy (ECO) for this level the temperature setpoints are taken from the comfort mode settings adding an offset; the fan speed and
damper opening setpoints instead are controlled by the following specific parameters:
- P01+P03 economy temperature setpoint heating mode
- P02+P04 economy temperature setpoint cooling mode
- P10 economy fan speed setpoint
- P15 economy mixing chamber damper setpoint
- Night-time (NIGHT) also for this level the temperature setpoints are taken from the comfort mode settings adding a specific offset;
the fan speed and damper opening setpoints instead are controlled by the following specific parameters:
- P01+P05 temperature setpoint night-time heating mode
- P02+P06 temperature setpoint night-time cooling mode
- P11 night-time fan speed setpoint
- P16 night-time mixing chamber damper setpoint
N.B. If there is a clock error, the manual mode is activated.
7.2.3 Holiday mode (t01 = 2 or 3)
If a temporary suspension of the time band operating mode is required (clock enabled and not incorrect) the Holiday mode can be
activated consisting of a set period starting when this is activated and ending at a particular date and time. The holiday mode can be
activated for a few hours or for several months as required, with the holiday ending date and time correctly set (parameters t33-t36),
after which there will be a return to the situation prior to the holiday mode setting.
The holiday mode can have two variants: with the machine on or with the machine off (the word OFFt appears on the display)
configured by setting parameter t01 to 2 or 3 respectively. The mode of operation starts when the parameter value is confirmed by
pressing the SET key.
In “Holiday ON” mode the manual mode setpoints are used:
P07 manual temperature setpoint heating mode
P08 manual temperature setpoint cooling mode
P12 manual fan setpoint
P17 manual mixing chamber damper setpoint

Table of Contents

Other manuals for Evco EV3 MVC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EV3 MVC and is the answer not in the manual?

Evco EV3 MVC Specifications

General IconGeneral
BrandEvco
ModelEV3 MVC
CategoryController
LanguageEnglish

Related product manuals