EasyManuals Logo

Evco EV3 MVC Applications Manual

Evco EV3 MVC
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 2.2c | Code 1443DMVCI224
page 57 of 74
Label Visibility default min max UM description
S03 U
Alarm in progress
0: OFF
1: ON
S04 U
Operating mode
0: Disabled
1: OFF
2: Comfort
3: Economy
4: Night
5: Holiday:
6: Manual
7: Holiday with machine off
255: None
S05 S 0 100 % Fan Regulation Setpoint
S06 S
Fan operating mode
0: Normal
1: Remote
2: CO2
3: Humidity
4: Forced by DI
5: OFF - External air damper awaited
6: Alarm
7: OFF
8: OFF from digital input (DI)
9: OFF from time band (TB)
10: External air limitation
11: Constant pressure
12: Constant capacity
13: OFF - Defrosting
14: ON - Defrosting
15: 15 = Post-ventilation
S07 U % Supply Fan Speed
S08 U % Return Fan Speed
S09 S 0 100 % Mixing chamber damper regulation setpoint
S10 S
Mixing chamber damper operating mode
0: Disabled
1: Normal
2: CO2
3: Humidity
4: Free cooling/heating
5: OFF
6: External air limitation
S11 S % Mixing chamber damper aperture
S12 S
Recovery heat exchanger operating mode
0: Disabled
1: OFF
2: ON
S13 S % Recovery heat exchanger percentage
S14 S
Recovery heat exchanger defrost phase
0: Not in defrost
3: Defrosting
5: Dripping
S15 U 0 100 80 %rH Humidity setpoint

Table of Contents

Other manuals for Evco EV3 MVC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EV3 MVC and is the answer not in the manual?

Evco EV3 MVC Specifications

General IconGeneral
BrandEvco
ModelEV3 MVC
CategoryController
LanguageEnglish

Related product manuals