EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 2.2c | Code 1443DMVCI224
page 41 of 74
Label
Default
value
Default
visibility
Min Max um Description
C47 5 S 0 255 % Humidity regulation band
C48 1 M 0 1
Dehumidifying in cooling mode with priority over heat
regulation
0: OFF
1: ON
C49 25 M 0 255 °C-°F Minimum humidifier supply temperature value
C50 1,000 S 0 5,000 ppm CO
2
over-modulation setpoint
C51 100 S 0 5,000 ppm CO
2
over-modulation band
C52 5 M 0 255 °C-°F Free-heating temperature differential setpoint
C53 5 M 0 255 °C-°F Free-cooling temperature differential setpoint
C54 1.0 M 0.0 25.5 °C-°F Free cooling/heating hysteresis
C55 5.0 M 0.0 25.5 °C-°F Off-band setpoint
C56 1,000 S -5,000 5,000 Pa-m3/h Control setpoint in constant pressure/flow
C57 50 S 0 5,000 Pa-m3/h Control band in constant pressure/flow
C58 0 S 0 1,000
Flow-rate coefficient
0: Control in constant pressure
C59 0 S 0 1
Temperature Measurement Unit
0: Celsius (°C)
1: Fahrenheit (°F)
C60 0 M 0 1
Enable external air limitation function
0: OFF
1: ON
C61 2 S 0 3
MODBUS baud rate
0: 2400
1: 4800
2: 9600
3: 19200
C62 2 S 0 2
MODBUS parity
0: None
1: Odd
2: Even
C63 0 S 0 1
MODBUS stop bits
0: 1 stop bit
1: 2 stop bit
C64 90 M 0 255 s Three-point Water Valve 2 Running Time
C65 1.0 S -10.0 100.0 °C-°F Pre-heating start setpoint
C66 1.0 S 0.0 25.5 °C-°F Pre-heating regulation band
C67 20 S 0 255 s*10 Maximum Pre-heating time
C68 1 M 0 1
Fire/smoke alarm regulation type
0: Fire
1: Smoke
DEF Defrosting parameters
d01 0 M 0 3
Refrigeration circuit defrost mode
0: OFF
1: ON
2: with compressor switched off
3: timed
d02 -5.0 M -10.0 100.0 °C-°F Refrigeration circuit defrost start setpoint
d03 20 M 0 255 min Refrigeration circuit defrost activation delay
d04 15.0 M -10.0 100.0 °C-°F Refrigeration circuit defrost end setpoint
d05 5 M 1 255 min Maximum refrigeration circuit defrost time
d06 60 M 0 255 s
Refrigeration circuit compressor/reversing valve waiting
time

Table of Contents

Other manuals for Evco EVD MVC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EVD MVC Series and is the answer not in the manual?

Evco EVD MVC Series Specifications

General IconGeneral
BrandEvco
ModelEVD MVC Series
CategoryController
LanguageEnglish

Related product manuals