Table 28. Command for accessing setup menus and adjusting values
1. Select the Setup Menus with the help of Function Codes
FormatFUNC <Function Code>
After “Enter”, the Setup Menu for the Function Code will be called.
The <Function Code>= 0~18
2. Command to query the Functions No
FormatFUNC?
After “Enter”, the unit’s “Function Code” appears on the PC screen.
3. Command to query the set value of the Function
FormatSETT?
After “Enter”, the existing set value of the function appears on the PC
screen.
4. Command to set or adjust the value of the Function
FormatSETT <value>
After “Enter”, the new value of the Function is set Choose the <value> of the
function.
6-1-4. Setting interface
1. OVP Setting <FUNC0>Set the Over Voltage Protection (OVP) and
shutdown.
Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model, 64 VDC @ 48V
Model
Model
Setting value range
12 V
15 VDC ~ 16 VDC
24 V
30 VDC ~ 32 VDC
48 V
60 VDC ~ 64 VDC
Table 29. OVP Setting <FUNC0>
2. OVP Recovery <FUNC1>When the DC input voltage is higher than the OVP
setting, the ECB-series shuts-down; once the input voltage falls below the
set OVP value, the ECB-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model, 60 VDC @ 48V
Model
Model
Setting value range
12 V
13 VDC ~ 15 VDC