Guidelines for DC Power in the VIPRION Platform
Platform Guide: VIPRION
®
6 - 7
System power consumption
The actual amount of power draw from the DC power source depends on the
type and number of blades and the redundancy configuration. Table 6.3
shows several possible configurations and their typical and maximum power
draw.
NEBS information
The following warning applies to the network equipment building system
(NEBS) version of the VIPRION platform.
WARNING
The intra-building interfaces of this platform, including Ethernet, are
suitable for connection to intra-building or unexposed wiring or cabling
only with shielded and grounded cables at both ends. The intra-building
ports of the equipment must not be metallically connected to interfaces that
connect to the outside plant (OSP) or its wiring.
Blade quantity and type
Typical system power
draw
Maximum system power
draw
Number of power
supplies installed
1 x PB100 400W 475W 2
2 x PB100 650W 800W 2
3 x PB100 1000W 1225W 4
4 x PB100 1250W 1550W 4
Table 6.3 DC Mains Total System Power Draw