Platform Specifications
Platform Guide: VIPRION
®
9 - 3
System power consumption
The actual amount of power draw from the AC source depends on the type
and number of blades and the power supply AC source voltage and
redundancy configuration. Tables 9.3 and 9.4 show several possible
configurations and their typical and maximum power draw.
Table 9.3 AC mains total system power draw (low-line input)
Table 9.4 AC mains total system power draw (high-line input)
Blade quantity and type
Typical system power
draw
Maximum system power
draw
Number of power
supplies installed
1 x PB100 650W 875W 2
2 x PB100 950W 1250W 2
3 x PB100 1300W 1625W 4
4 x PB100 1600W 2000W 4
1 x PB200 675W 900W 2
2 x PB200 1000W 1300W 2
3 x PB200 1375W 1700W 4
4 x PB200 1700W 2100W 4
Blade quantity and type
Typical system power
draw
Maximum system power
draw
Number of power
supplies installed
1 x PB100 675W 900W 2
2 x PB100 975W 1275W 2
3 x PB100 1325W 1650W 4
4 x PB100 1625W 2025W 4
1 x PB200 700W 925W 2
2 x PB200 1025W 1325W 2
3 x PB200 1400W 1725W 4
4 x PB200 1725W 2125W 4