E124S 38 532434 - Rev.A
Translation of the original instructions
ENGLISH
CYCLE COUNTER
READING THE CYCLES PERFORMED COUNTER
Add together the readings of functions
nc (thou-
sands) and
nd (tens) in ADVANCED programming.
RESETTING THE CYCLE COUNTER
In ADVANCED programming, with the function
AS
=
no, go to function nc and press ++ and
--
for 5 s.
MAINTENANCE REQUESTED
It is possible to program the number of cycles after
which maintenance is required.
When the automation reaches the set number of
cycles, there is a pre-flashing of at least 8 s at each
movement. The user should ask the installer to carry
out maintenance.
1. In ADVANCED programming, function
AS, se-
lect
Y to enable the maintenance request.
2. In function
nc set the value in thousands using
the
++ and
--
buttons.
3. In function
nd set the value in tens using the ++
and
--
buttons.
4. Exit and save the programming.
14.2 RESTORING FACTORY SETTINGS
The procedure:
- restores all the default settings of the board
- deletes the SETUP
- deletes all the radio controls
- resets the cycle counter
1. With the board not powered, switch on mains
power (the MAIN LED lights up).
2. A few seconds after having been switched on,
while the display shows the FW version (e.g.
4.0),
press and hold down the buttons ++,
--
, FF simul-
taneously.
- After approximately 10 s,
-- appears on the dis-
play and LEDS R1 and R2 light up.
3. Release the buttons.
- LEDs R1 and R2 switch off.
- After approximately 10 s,
S0 flashes on the display
(SETUP required).