2. Commissioning
2−53
Festo P.BE−CPX−FB38−EN en 0804NH
Proceed as follows
· Check the DIL switch settings as well as the hardware and
network configuration before using and replacing the bus
node or CPX terminal.
· Make sure that the desired parameterisation of the CPX
terminal is automatically carried out in the start−up"
phase, that is, during initialisation (EtherCAT status
Initialisation), (see section 2.6.2).
Please note
Perform configuration and parameterisation again after a
module replacement!
Recreate the necessary hardware and network configur
ation and CPX terminal parameterisation after replacement
of the bus node or CPX terminal.
To do this, use the EtherCAT controller or the Festo
Maintenance Tool (CPX−FMT) or handheld unit (CPX−MMI).
CPX−specific configuration and parameter data can
be
entered only with CPX−FMT or CPX−MMI.
· Check the parameterisation, using spot checks if
necessary.